Connecting The Ground Bonding Cable - HP R1500 - UPS XR User Manual

Hp 3 phase ups user guide
Table of Contents

Advertisement

Power Bus Bar
terminal block
Output
Input
Neutral
Safety ground
*Use 13.3 mm

Connecting the ground bonding cable

The ground bonding screw is provided as an attachment point for conductors. Use a ground bonding cable
if the rack contains any conductors for the purpose of functional grounding or bonding of ungrounded metal
parts.
Terminal
Power Bus Bar wire
position
function
1
Phase 1 out
2
Phase 2 out
3
Phase 3 out
4
Phase 1 in
5
Phase 2 in
6
Phase 3 in
7
Neutral
8
Neutral
9
Neutral
10
Ground
2
(6 AWG) 90º C copper wire minimum.
Terminal wire size
Tightening torque
rating*
13.3 mm
2
(6 AWG)
31.1 Nm (275 lb in)
to 177 mm
2
(350
kcmil)
13.3 mm
2
(6 AWG)
31.1 Nm (275 lb in)
to 177 mm
2
(350
kcmil)
13.3 mm
2
(6 AWG)
31.1 Nm (275 lb in)
to 177 mm
2
(350
kcmil)
13.3 mm
2
(6 AWG)
31.1 Nm (275 lb in)
to 177 mm
(350
2
kcmil)
13.3 mm
2
(6 AWG)
31.1 Nm (275 lb in)
to 177 mm
(350
2
kcmil)
13.3 mm
2
(6 AWG)
31.1 Nm (275 lb in)
to 177 mm
(350
2
kcmil)
13.3 mm
(6 AWG)
31.1 Nm (275 lb in)
2
to 177 mm
(350
2
kcmil)
13.3 mm
(6 AWG)
2
31.1 Nm (275 lb in)
to 177 mm
(350
2
kcmil)
13.3 mm
(6 AWG)
31.1 Nm (275 lb in)
2
to 177 mm
(350
2
kcmil)
18 mm
(4 AWG) to
1.8 (16 lb in)
2
215mm
(400 kcmil)
2
UPS installation 29