Setting The Battery Low Alarm Level - HP R1500 - UPS XR User Manual

Hp 3 phase ups user guide
Table of Contents

Advertisement

Description
Delay
Site Wiring Fault Notice
Reset Custom Event Settings
REPO Configuration

Setting the Battery Low alarm level

The default Battery Low alarm level setting provides approximately 2.5 minutes of battery warning for a UPS.
Additional ERMs installed in a parallel system can provide a longer warning time.
To set the Battery Low Alarm Level:
Press any button to activate the menu options.
1.
Select SETTINGS > USER SETTINGS > BATTERY SETUP > Automatic Battery Tests.
2.
Use the up or down arrow buttons to select the volts per cell. For a list of settings, see the table below.
3.
Press the left arrow button to save the setting.
4.
Press and hold the ESC button until the Start screen appears.
5.
Warning time
(in minutes)
2
2
2
2
3
3
3
3
4
4
4
4
5
5
5
5
Values are approximate.
Available settings
[Enabled][Disabled]
0 through 32
[Enabled][Disabled]
Number of ERMs
Battery Low Alarm Level (user setting)
installed
20% Load
1
1.783
2
1.776
3
1.772
4
1.768
1
1.805
2
1.793
3
1.787
4
1.781
1
1.822
2
1.807
3
1.789
4
1.793
1
1.835
2
1.818
3
1.799
4
1.803
Default setting
Enabled
Total: 0/32
Enabled
50% Load
100% Load
1.821
1.854
1.811
1.831
1.798
1.818
1.781
1.805
1.848
1.981
1.833
1.859
1.820
1.843
1.803
1.831
1.868
1.918
1.850
1.883
1.836
1.866
1.818
1.850
1.884
1.941
1.863
1.903
1.849
1.883
1.823
1.865
UPS operations 70