9.3
Sample III. Connecting the SISTORE AX and SCU
Siemens Building Technologies
Fire & Security Products
RS232-Current
PT40P
CDC0402
Loop Converter
TTY
Configuration of SISTORE AX:
In the RS232/RS485 menu:
RS485: Baud Rate: 2400
Parity: Even
Data: 8
Stop: 1
Usage: PTZ Control
In the „Camera" menu:
Camera setting:
PTZ Device: Siemens SCU
ID: 1
Configuration of the Roline RS232<->RS485 Converter:
T-RTS
Rx ON
DTE (or DCE; must not be identical with the other converter)
Configuration of the RS232<->Current Loop Converter:
20 (mA)
Rx ACT (Active)
Tx ACT (Active)
DCE (or DTE; must not be identical with the other converter)
(If the two converters are connected using a cross-over cable,
either DCE or DTE must be set on both converters.)
Appendix E — Connection Diagram
RS232-RS485
Converter
RS485
AXAX9/AX16
SISTORE AX9 AX16_EN.doc
09.2004