Two Stage Acceleration and Deceleration
When terminal [2CH] is turned ON, the inverter
changes
the
deceleration from the initial settings
F003) to use the second set of acceleration/
deceleration values. When the terminal is
turned OFF, the inverter is returned to the
original acceleration and deceleration time
(F002
acceleration
deceleration time 1). Use
A093
time 2) and
the second stage acceleration and deceleration
times.
In the graph shown above, the [2CH] becomes active during the initial acceleration. This
causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).
Option
Terminal
Function Name
Code
Symbol
09
2CH
Two-stage Accelera-
tion and
Deceleration
C001~C007
Valid for inputs:
A092, A093,
Required settings
Notes:
A094
Function
selects the method for second
stage acceleration. It must be set =
the input terminal method in order for the [2CH]
terminal assignment to operate.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
rate
of
acceleration
(F002
time
1,
and
A092
(acceleration
(deceleration time 2) to set
State
ON
OFF
A094=00
00
to select
33
and
and
Output
frequency
1
[2CH]
F003
0
1
[FW,RV]
0
Description
Frequency output uses 2nd-stage acceleration and
deceleration values
Frequency output uses the initial acceleration 1 and
deceleration 1 values
Example (default input configuration shown—see
page
3–49):
2CH
7
6
5
4
See I/O specs on
page 4–6.
Target
frequency
second
initial
t
3
2
1
L
PCS
PLC
P24