Func.
Name
Code
C047
Pulse train input/output
scale conversion
C052
PID FBV output
high limit
C053
PID FBV output
low limit
C054
Over-torque/under-torque
selection
C055
Over/under-torque level
(Forward powering mode)
C056
Over/under-torque level
(Reverse regen. mode)
C057
Over/under-torque level
(Reverse powering mode)
C058
Over/under-torque level
(Forward regen. mode)
C059
Signal output mode of
Over/under-torque
C061
Electronic thermal warning
level
C063
Zero speed detection level
C064
Heat sink overheat warning
C071
Communication speed
C072
Modbus address
C074
Communication parity
C075
Communication stop bit
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"C" Function
Description
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in × (C047)
Set range is 0.01 to 99.99
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0
to 100%
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
Two option codes:
00...Over-torque
01...Under-torque
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Two option codes:
00...During accel., decel. and
constant speed
01...During constant speed only
Set range is 0 to 100%
Setting 0 means disabled.
Set range is 0.0 to 100.0Hz
Set range is 0 to 110 °C
Eight option codes:
03...2,400 bps
04...4,800 bps
05...9,600 bps
06...19,200 bps
07...38,400 bps
08...57,600 bps
09...76,800 bps
10...115,200 bps
Set the address of the inverter on
the network. Range is 1 to 247
Three option codes:
00...No parity
01...Even parity
02...Odd parity
Two option codes:
1...1 bit
2...2 bit
68
Run
Defaults
Mode
Lnitial data
Units
Edit
1.00
100.0
%
0.0
%
00
-
100.
%
100.
%
100.
%
100.
%
01
-
90
%
0.00
Hz
°C
100.
05
baud
1.
00
1
bit