Hitachi WJ200 Series Quick Reference Manual page 67

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Intelligent Terminal Functions
Func.
Name
Code
C001
Input [1] function
C002
Input [2] function
C003
Input [3] function
[GS1 assignable]
C004
Input [4] function
[GS2 assignable]
C005
Input [5] function
[PTC assignable]
C006
Input [6] function
C007
Input [7] function
C011
Input [1] active state
C012
Input [2] active state
C013
Input [3] active state
C014
Input [4] active state
C015
Input [5] active state
C016
Input [6] active state
C017
Input [7] active state
C021
Output [11] function
[EDM assignable]
C022
Output [12] function
C026
Alarm relay function
C027
[EO] terminal selection
(Pulse/PWM output)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"C" Function
Description
Select input terminal [1] function,
68 options (see next section)
Select input terminal [2] function,
68 options (see next section)
Select input terminal [3] function,
68 options (see next section)
Select input terminal [4] function,
68 options (see next section)
Select input terminal [5] function,
68 options (see next section)
Select input terminal [6] function,
68 options (see next section)
Select input terminal [7] function,
68 options (see next section)
Select logic conversion, two option
codes:
00...normally open [NO]
01...normally closed [NC]
48 programmable functions
available for logic (discrete) outputs
(see next section)
48 programmable functions
available for logic (discrete) outputs
(see next section)
13 programmable functions:
00...Output frequency (PWM)
01...Output current (PWM)
02...Output torque (PWM)
03...Output frequency (Pulse train)
04...Output voltage (PWM)
05...Input power (PWM)
06...Electronic thermal load ratio
(PWM)
07...LAD frequency (PWM)
08...Output current (Pulse train)
10...Heat sink temperature (PWM)
12...General output (PWM)
15...Pulse train input monitor
16...Option(PWM)
66
Run
Defaults
Mode
Lnitial data
Units
Edit
00
[FW]
01
[RV]
02
[CF1]
03
[CF2]
09
[2CH]
18
[RS]
13
[USP]
00
00
00
00
00
00
00
01
[FA1]
00
[RUN]
05
[AL]
07

Hide quick links: