Monitoring functions
NOTE:. Mark " " in b031=10 shows the accessible parameters when b031 is set "10", high
level access.
Func.
Code
D001
Output frequency monitor
D002
Output current monitor
D003
Rotation direction monitor
D004
Process variable (PV),
PID feedback monitor
D005
Intelligent input
terminal status
D006
Intelligent output
terminal status
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"d" Function
Name
Real time display of output frequency
to motor from
0.0 to 400.0Hz
If b163 is set high, output frequency
(F001) can be changed by up/down
key with d001 monitoring.
Filtered display of output current to
motor, range is
0 to 655.3 ampere (~99.9 ampere for
1.5kW and less)
Three different indications:
"F" ...Forward
"o" ...Stop
"r" ...Reverse
Displays the scaled PID process
variable (feedback) value (A075 is
scale factor),
0.00 to 10000
Displays the state of the intelligent
input terminals:
Displays the state of the intelligent
output terminals:
46
Description
ON
OFF
7
6 5 4
3
2
1
Terminal numbers
ON
OFF
Relay
12 11
Run
Units
Mode
Edit
−
Hz
−
A
−
−
−
% times
constant
−
−
−
−