Hitachi WJ200 Series Quick Reference Manual page 55

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
Func.
Code
DC braking time at start
a058
Carrier frequency during DC
a059
braking
Frequency upper limit
A061
Frequency upper limit,
A261
2nd motor
Frequency lower limit
A062
Frequency lower limit,
A262
2nd motor
Jump freq. (center) 1 to 3
A063
A065
A067
Jump freq. width (hysteresis) 1
A064
to 3
A066
A068
Acceleration hold frequency
A069
Acceleration hold time
A070
PID enable
A071
CALL NOW 800-985-6929
http://www.automatedpt.com
"A" Function
Name
Sets the duration for DC braking,
range
seconds
Carrier frequency of DC braking
performance, range is from 2.0 to
15.0kHz
Sets a limit on output frequency
less than the maximum
frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
less than the maximum
frequency (A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
Up to 3 output frequencies can
be defined for the output to jump
past to avoid motor resonances
(center frequency)
Range is 0.0 to 400.0 Hz
Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
Sets the frequency to hold
acceleration, range is 0.0 to
400.0Hz
Sets the duration of acceleration
hold, range is 0.0 to 60.0
seconds
Enables PID function,
three option codes:
00...PID Disable
01...PID Enable
02...PID Enable with reverse
output
http://www.automatedpt.com
Mode
Description
is
from
0.0
to
60.0
53
Email: charles@automatedpt.com
Run
Defaults
Lnitial data
Units
Edit
0.0
sec.
5.0
sec.
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.0
Hz
0.0
0.0
0.5
Hz
0.5
0.5
0.00
Hz
0.0
sec.
00