Figure 6-19
Connecting the dV/dt filter compact plus voltage peak limiter - separate components
Cable cross-sections
In a dV/dt filter with separate voltage peak limiter (type 4), the connections between dV/dt
reactor and voltage peak limiter are already installed on the voltage peak limiter.
Table 6- 32
Table 6- 33
Cable type: 600 V, UL style 3271, operating temperature 125° C
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Cable cross-sections for connections between a dV/dt filter and Motor Module
dV/dt filter compact plus
voltage peak limiter
Type 1
Type 2
Type 3
Type 4
Connection cable enclosed for connecting dV/dt reactor and voltage peak limiter
Voltage peak limiter
Type 4
6.4 dv/dt filter compact plus Voltage Peak Limiter
Cross-section
[mm²]
16
25
50
95
Cross-section
Lug for connecting 1U2 / 1V2 / 1W2 on the dV/dt
[mm²]
70
Motor-side power components
Connection on dV/dt filter
Screw M8 / 12 Nm
Screw M8 / 12 Nm
Copper bar for M8 bolt / 12 Nm
Copper bar for M8 bolt / 12 Nm
reactor
M12
M
3~
291