X9 Terminal Strip; X41 Ep Terminal / Temperature Sensor Connection - Siemens SINAMICS S120 Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
3.4 Active Line Modules
3.4.3.4

X9 terminal strip

Table 3- 32
Terminal strip X9
Terminal
1
2
3
4
5
6
L1
L2
Max. connectable cross-section: Terminals 1 ... 6: 1.5 mm
Note
Connecting fan supply, with frame sizes FX and GX
The fan supply for frame sizes FX and GX is connected directly to fuse holders -F10 and
-F11.
3.4.3.5

X41 EP terminal / temperature sensor connection

Table 3- 33
Terminal strip X41
Terminal
1
2
3
4
Max. connectable cross-section 1.5 mm
Note
Connection to terminals 1 and 2
For operation, 24 VDC must be connected to terminal 2 and ground to terminal 1. Pulse
suppression is activated when removed.
158
Signal name
P24V
M
Bypass contactor control
Pre-charge contactor control
Connection for fan supply
(frame sizes HX and JX only)
Function
EP M1 (Enable Pulses)
EP +24 V (Enable Pulses)
- Temp
+ Temp
2
Technical specifications
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: max. 1.7 A
for Active Interface Module, X609:11
for Active Interface Module, X609:12
for Active Interface Module, X609:9
for Active Interface Module, X609:10
AC 380 ... 480 V / AC 500 ... 690 V
Current consumption: See Technical data
, Terminals L1 - L2: 35 mm
2
Technical specifications
Supply voltage: 24 VDC (20.4 ... 28.8 V)
Current consumption: 10 mA
Temperature sensor connection KTY84-1C130/PTC
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
2