Table 2- 14
Technical data of line reactors for Basic Line Modules, 3 AC 500 ... 690 V, Part 1
Order number
Suitable for
Basic Line Module
Rated power of the Basic
Line Module
Rated voltage
I
thmax
Power loss
Line/load connection
1U1, 1V1, 1W1, 1U2, 1V2,
1W2
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Weight
Table 2- 15
Technical data of line reactors for Basic Line Modules, 3 AC 500 ... 690 V, Part 2
Order number
Suitable for
Basic Line Module
Rated power of the Basic
Line Module
Rated voltage
I
thmax
Power loss
Line/load connection
1U1, 1V1, 1W1, 1U2, 1V2,
1W2
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Weight
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
6SL3000-
0CH32-7AA0
6SL3330-
1TG33-0AAx
kW
250
V
A
270
kW
0.277
M10 connecting
lugs
M6 screw
IP00
mm
270
mm
248
mm
200
kg
27.9
6SL3000-
0CH41-2AA0
6SL3330-
1TG41-4AAx
kW
1100
V
A
1167
kW
0.783
M12 connecting
lugs
M6 screw
IP00
mm
460
mm
435
mm
235
kg
147
2.4 Line reactors for Basic Line Modules
0CH34-8AA0
1TG34-3AAx
355
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
482
0.478
M12 connecting
lugs
M6 screw
IP00
350
321
232.5
55.6
0CH41-6AA0
1TG41-8AAx
1500
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
1600
0.977
M12 connecting
lugs
M6 screw
IP00
416
435
250
134
Line-side power components
0CH36-0AA0
0CH41-2AA0
1TG36-8AAx
1TG41-1AAx
560
597
0.485
M12 connecting
M12 connecting
lugs
M6 screw
M6 screw
IP00
350
321
232.5
63.8
900
1167
0.783
lugs
IP00
460
435
235
147
53