Advertisement

NOTE
• Set consecutive numbers for the station numbers. (Do not skip a number in sequence like "station number 1 - station
number 2- station number 4".)
The station number does not have to match with the physical connection sequence. (There is no problem with having
the physical connection sequence like "station number 1 - station number 3 - station number 4 - station number 2".)
• One inverter occupies one station. (One remote device station)
• "L.ERR" LED flickers if the setting is changed. When power is switched on again or the RES signal is turned on, the
setting value is reflected and the LED turns off.
4.5.2

Baud rate setting (Pr.543)

Set the transmission speed. (Refer to the manual for the CC-Link master module for details of transmission speed.)
Pr.
543
Baud rate selection (CC-Link)
NOTE
• "L.ERR" LED flickers if the setting is changed. When power is switched on again or the RES signal is turned on, the
setting value is reflected and the LED turns off.
38
INVERTER SETTING
Name
Initial value
0
Setting range
Transmission speed
0
156 kbps
1
625 kbps
2
2.5 Mbps
3
5 Mbps
4
10 Mbps