Input Signals (Inverter (Fr-A8Nc) To Master Module) - Mitsubishi Electric FR-A8NC Instruction Manual

Plug-in option cc-link communication function
Hide thumbs Also See for FR-A8NC:
Table of Contents

Advertisement

7.1.2

Input signals (inverter (FR-A8NC) to master module)

The input signals to the master module are indicated. (Output signals from inverter)
Device no.
RX0
Forward running
RX1
Reverse running
RX2
Running (terminal RUN function)
RX3
Up to frequency (terminal SU function)
RX4
Overload alarm (terminal OL function)
Instantaneous power failure (terminal IPF
RX5
function)

RX6
Frequency detection (terminal FU function)
RX7
Fault (terminal ABC1 function)
RX8
― (terminal ABC2 function)
RX9
― (DO0 function)
RXA
― (DO1 function)
RXB
― (DO2 function)
RXC
Monitoring
Signal









Description
0: Other than forward running (during stop or reverse rotation)
1: Forward running
0: Other than reverse running (during stop or forward rotation)
1: Reverse running
Functions assigned to terminals RUN, SU, OL, IPF, FU, ABC1 and ABC2
activate.
Functions assigned to Pr.313 to Pr.315 are activated.
After "1" is set in the monitor command (RYC), and the monitored value is
set in the remote register Rwr0, 1, 4 to 7, "1" is set in this signal. When "0" is
set in the monitor command (RYC), "0" is set in this signal.