TOSHIBA SERVICE MANUAL AIR CONDITIONER HEAT PUMP MULTI SPLIT (2-PIPE) Outdoor Units MAR - M81HTM8 - E MAR - M101HTM8 - E Multi Controllers RBM - Y1032E - E RBM - Y1042E - E AUGUST 1997 Page 1...
TOSHIBA Contents 1. Specifications Outdoor Unit Multi Controller 2. Basic Permutations / Capabilities 3. Dimensional Views Outdoor Unit Multi Controller 4. Wiring Diagrams Outdoor Unit Multi Controller 5. Refrigeration Circuit Outdoor Unit Multi Controller 6. Display Information and Fault Codes 7.
TOSHIBA 1. Specifications OUTDOOR UNITS Model MAR-M81HTM8-E MAR-M101HTM8-E Cooling Capacity 20.0 (22.4) 25.0 (28.0) Heating Capacity 20.0 (25.0) 25.0 (31.5) Power Supply 3ph,380/415v,50Hz Power Consumption (C/H) kW 8.0 / 7.7 10.1 / 10.1 Running Current (C/H) Amps 12.3 / 11.7 15.7 / 15.0...
Page 4
TOSHIBA 1. Specifications MULTI CONTROLLERS Model RBM-Y1032E-E RBM-Y1042E-E Number of Branches Gas Pipe (Inlet) Inch 1 1/8 1 1/8 Liquid Pipe (Inlet) Inch Branch Pipes (Gas) Inch 3/4 x 3 3/4 x 4 Branch Pipes (Liquid) Inch 3/8 x 3...
Page 5
TOSHIBA 2. Basic Permutations of Indoor to Outdoor Units The indoor units are given a code number according to their capacity rank - see below Model Number Code Number RAV103 RAV132/133 RAV453/160/1/2/3 RAV202/3 RAV713/260/1/2/3 RAV1003/360/1/2/3 RAV1253/460/1/2/3 Multiple indoor units may be connected to one outdoor unit, providing the total indoor code does not exceed the outdoor unit code number.
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1032E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more...
Page 8
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1042E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more or more...
Page 9
TOSHIBA 4. Schematic Wiring Diagrams Outdoor Unit Reactor Giant Electric Starter Contactor Transistor Rectifier Smoothing Circuit 52C1 λ 2200 F/400v x 2 47k Ω /20W x 2 ℜ Noise Filter Contactor 52C2 U V W 1 2 3 4 ℜ...
TOSHIBA 6. Fault Code and Display Information Fault Codes Before reading the fault codes do not turn the power off as doing so will wipe the diagnostic memory. Caution must be taken when removing the access covers as high voltages are present.
Page 14
TOSHIBA 6. Fault Code and Display Information Display switch information Multicontroller Switch position Information System Communication Fault Codes Level of Demand Oil Retrieval, Superheat, Defrost Operating Mode Restart Timer Circuit Test (commissioning only) PMV(A) Position PMV(B) Position PMV(C) Position PMV(D) Position...
Page 15
TOSHIBA 6. Fault Code and Display Information Multi Controller Display Switch Information Switch Indicates LD 1 LD 2 Pos. |_| | |_ _ |_| | |_ _ |_| | |_ _ |_| | |_ _ Serial From B To B...
Page 16
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information The operating status of the outdoor unit and fault diagnosis can be made using both the display selector switch (on the interface pcb) and the eight red light emitting diodes on the interface printed circuit board.
Page 17
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information cont. d. Display switch set to position “3” identifies a fault condition in the outdoor unit. Details are in the fault code chart on page 13 e. Display switch set to positions “4, 5, 6 & 7” identifies the indoor unit capacity code for each branch.
TOSHIBA 7. Circuit Test Procedure These systems have a feature which enables them to check that the wiring and piping connections are aligned with each other. This is carried out by allowing refigerant flow to one indoor unit at a time and monitoring that indoor unit’s coil sensor for a corresponding drop in temperature.
Page 20
TOSHIBA SERVICE MANUAL AIR CONDITIONER HEAT PUMP MULTI SPLIT (2-PIPE) Outdoor Units MAR - M81HTM8 - E MAR - M101HTM8 - E Multi Controllers RBM - Y1032E - E RBM - Y1042E - E AUGUST 1997 Page 1...
TOSHIBA Contents 1. Specifications Outdoor Unit Multi Controller 2. Basic Permutations / Capabilities 3. Dimensional Views Outdoor Unit Multi Controller 4. Wiring Diagrams Outdoor Unit Multi Controller 5. Refrigeration Circuit Outdoor Unit Multi Controller 6. Display Information and Fault Codes 7.
TOSHIBA 1. Specifications OUTDOOR UNITS Model MAR-M81HTM8-E MAR-M101HTM8-E Cooling Capacity 20.0 (22.4) 25.0 (28.0) Heating Capacity 20.0 (25.0) 25.0 (31.5) Power Supply 3ph,380/415v,50Hz Power Consumption (C/H) kW 8.0 / 7.7 10.1 / 10.1 Running Current (C/H) Amps 12.3 / 11.7 15.7 / 15.0...
Page 23
TOSHIBA 1. Specifications MULTI CONTROLLERS Model RBM-Y1032E-E RBM-Y1042E-E Number of Branches Gas Pipe (Inlet) Inch 1 1/8 1 1/8 Liquid Pipe (Inlet) Inch Branch Pipes (Gas) Inch 3/4 x 3 3/4 x 4 Branch Pipes (Liquid) Inch 3/8 x 3...
Page 24
TOSHIBA 2. Basic Permutations of Indoor to Outdoor Units The indoor units are given a code number according to their capacity rank - see below Model Number Code Number RAV103 RAV132/133 RAV453/160/1/2/3 RAV202/3 RAV713/260/1/2/3 RAV1003/360/1/2/3 RAV1253/460/1/2/3 Multiple indoor units may be connected to one outdoor unit, providing the total indoor code does not exceed the outdoor unit code number.
Page 25
TOSHIBA CONSTRUCTION VIEWS MAR-M81HTM8E-E MAR-M101FHTM8E-E 98 mm 790 mm 824 mm 90 mm 750 mm 610 mm 375 mm 130 mm 160 mm AUGUST 1997 Page 6...
Page 26
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1032E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more...
Page 27
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1042E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more or more...
Page 28
TOSHIBA 4. Schematic Wiring Diagrams Outdoor Unit Reactor Giant Electric Starter Contactor Transistor Rectifier Smoothing Circuit 52C1 λ 2200 F/400v x 2 47k Ω /20W x 2 ℜ Noise Filter Contactor 52C2 U V W 1 2 3 4 ℜ...
Page 30
TOSHIBA 5. Schematic Refrigeration Diagram Outdoor Unit INVERTER COMPRESSOR H.P. SWITCH EXPANSION SERVICE VALVE PRESSURE VALVE ThD1 SENSOR PRESSURE INVERTER SWITCH COMPRESSOR DRIER LIQUID TANK HEAT CHECK VALVE EXCHANGER D.O.L. COMPRESSOR ThD2 HIGH PRESSURE RELEASE 4-WAY VALVE D.O.L. SERVICE H.P.SWITCH...
Page 31
TOSHIBA 5. Schematic Refrigeration Diagram Multi Controller INDOOR UNIT EXPANSION VALVE PMV(A) STRAINER BRANCH A CHECK VALVE EXPANSION VALVE PMV(B) LIQUID PIPE STRAINER STRAINER BRANCH B CHECK VALVE EXPANSION VALVE PMV(C) STRAINER BRANCH C CHECK VALVE EXPANSION VALVE PMV(D) STRAINER...
Page 32
TOSHIBA 6. Fault Code and Display Information Fault Codes Before reading the fault codes do not turn the power off as doing so will wipe the diagnostic memory. Caution must be taken when removing the access covers as high voltages are present.
Page 33
TOSHIBA 6. Fault Code and Display Information Display switch information Multicontroller Switch position Information System Communication Fault Codes Level of Demand Oil Retrieval, Superheat, Defrost Operating Mode Restart Timer Circuit Test (commissioning only) PMV(A) Position PMV(B) Position PMV(C) Position PMV(D) Position...
Page 34
TOSHIBA 6. Fault Code and Display Information Multi Controller Display Switch Information Switch Indicates LD 1 LD 2 Pos. |_| | |_ _ |_| | |_ _ |_| | |_ _ |_| | |_ _ Serial From B To B...
Page 35
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information The operating status of the outdoor unit and fault diagnosis can be made using both the display selector switch (on the interface pcb) and the eight red light emitting diodes on the interface printed circuit board.
Page 36
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information cont. d. Display switch set to position “3” identifies a fault condition in the outdoor unit. Details are in the fault code chart on page 13 e. Display switch set to positions “4, 5, 6 & 7” identifies the indoor unit capacity code for each branch.
Page 37
TOSHIBA 7. Circuit Test Procedure These systems have a feature which enables them to check that the wiring and piping connections are aligned with each other. This is carried out by allowing refigerant flow to one indoor unit at a time and monitoring that indoor unit’s coil sensor for a corresponding drop in temperature.
Page 39
TOSHIBA SERVICE MANUAL AIR CONDITIONER HEAT PUMP MULTI SPLIT (2-PIPE) Outdoor Units MAR - M81HTM8 - E MAR - M101HTM8 - E Multi Controllers RBM - Y1032E - E RBM - Y1042E - E AUGUST 1997 Page 1...
Page 40
TOSHIBA Contents 1. Specifications Outdoor Unit Multi Controller 2. Basic Permutations / Capabilities 3. Dimensional Views Outdoor Unit Multi Controller 4. Wiring Diagrams Outdoor Unit Multi Controller 5. Refrigeration Circuit Outdoor Unit Multi Controller 6. Display Information and Fault Codes 7.
Page 41
TOSHIBA 1. Specifications OUTDOOR UNITS Model MAR-M81HTM8-E MAR-M101HTM8-E Cooling Capacity 20.0 (22.4) 25.0 (28.0) Heating Capacity 20.0 (25.0) 25.0 (31.5) Power Supply 3ph,380/415v,50Hz Power Consumption (C/H) kW 8.0 / 7.7 10.1 / 10.1 Running Current (C/H) Amps 12.3 / 11.7 15.7 / 15.0...
Page 42
TOSHIBA 1. Specifications MULTI CONTROLLERS Model RBM-Y1032E-E RBM-Y1042E-E Number of Branches Gas Pipe (Inlet) Inch 1 1/8 1 1/8 Liquid Pipe (Inlet) Inch Branch Pipes (Gas) Inch 3/4 x 3 3/4 x 4 Branch Pipes (Liquid) Inch 3/8 x 3...
Page 43
TOSHIBA 2. Basic Permutations of Indoor to Outdoor Units The indoor units are given a code number according to their capacity rank - see below Model Number Code Number RAV103 RAV132/133 RAV453/160/1/2/3 RAV202/3 RAV713/260/1/2/3 RAV1003/360/1/2/3 RAV1253/460/1/2/3 Multiple indoor units may be connected to one outdoor unit, providing the total indoor code does not exceed the outdoor unit code number.
Page 44
TOSHIBA CONSTRUCTION VIEWS MAR-M81HTM8E-E MAR-M101FHTM8E-E 98 mm 790 mm 824 mm 90 mm 750 mm 610 mm 375 mm 130 mm 160 mm AUGUST 1997 Page 6...
Page 45
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1032E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more...
Page 46
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1042E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more or more...
Page 47
TOSHIBA 4. Schematic Wiring Diagrams Outdoor Unit Reactor Giant Electric Starter Contactor Transistor Rectifier Smoothing Circuit 52C1 λ 2200 F/400v x 2 47k Ω /20W x 2 ℜ Noise Filter Contactor 52C2 U V W 1 2 3 4 ℜ...
Page 49
TOSHIBA 5. Schematic Refrigeration Diagram Outdoor Unit INVERTER COMPRESSOR H.P. SWITCH EXPANSION SERVICE VALVE PRESSURE VALVE ThD1 SENSOR PRESSURE INVERTER SWITCH COMPRESSOR DRIER LIQUID TANK HEAT CHECK VALVE EXCHANGER D.O.L. COMPRESSOR ThD2 HIGH PRESSURE RELEASE 4-WAY VALVE D.O.L. SERVICE H.P.SWITCH...
Page 50
TOSHIBA 5. Schematic Refrigeration Diagram Multi Controller INDOOR UNIT EXPANSION VALVE PMV(A) STRAINER BRANCH A CHECK VALVE EXPANSION VALVE PMV(B) LIQUID PIPE STRAINER STRAINER BRANCH B CHECK VALVE EXPANSION VALVE PMV(C) STRAINER BRANCH C CHECK VALVE EXPANSION VALVE PMV(D) STRAINER...
Page 51
TOSHIBA 6. Fault Code and Display Information Fault Codes Before reading the fault codes do not turn the power off as doing so will wipe the diagnostic memory. Caution must be taken when removing the access covers as high voltages are present.
Page 52
TOSHIBA 6. Fault Code and Display Information Display switch information Multicontroller Switch position Information System Communication Fault Codes Level of Demand Oil Retrieval, Superheat, Defrost Operating Mode Restart Timer Circuit Test (commissioning only) PMV(A) Position PMV(B) Position PMV(C) Position PMV(D) Position...
Page 53
TOSHIBA 6. Fault Code and Display Information Multi Controller Display Switch Information Switch Indicates LD 1 LD 2 Pos. |_| | |_ _ |_| | |_ _ |_| | |_ _ |_| | |_ _ Serial From B To B...
Page 54
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information The operating status of the outdoor unit and fault diagnosis can be made using both the display selector switch (on the interface pcb) and the eight red light emitting diodes on the interface printed circuit board.
Page 55
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information cont. d. Display switch set to position “3” identifies a fault condition in the outdoor unit. Details are in the fault code chart on page 13 e. Display switch set to positions “4, 5, 6 & 7” identifies the indoor unit capacity code for each branch.
Page 56
TOSHIBA 7. Circuit Test Procedure These systems have a feature which enables them to check that the wiring and piping connections are aligned with each other. This is carried out by allowing refigerant flow to one indoor unit at a time and monitoring that indoor unit’s coil sensor for a corresponding drop in temperature.
Page 58
TOSHIBA SERVICE MANUAL AIR CONDITIONER HEAT PUMP MULTI SPLIT (2-PIPE) Outdoor Units MAR - M81HTM8 - E MAR - M101HTM8 - E Multi Controllers RBM - Y1032E - E RBM - Y1042E - E AUGUST 1997 Page 1...
Page 59
TOSHIBA Contents 1. Specifications Outdoor Unit Multi Controller 2. Basic Permutations / Capabilities 3. Dimensional Views Outdoor Unit Multi Controller 4. Wiring Diagrams Outdoor Unit Multi Controller 5. Refrigeration Circuit Outdoor Unit Multi Controller 6. Display Information and Fault Codes 7.
Page 60
TOSHIBA 1. Specifications OUTDOOR UNITS Model MAR-M81HTM8-E MAR-M101HTM8-E Cooling Capacity 20.0 (22.4) 25.0 (28.0) Heating Capacity 20.0 (25.0) 25.0 (31.5) Power Supply 3ph,380/415v,50Hz Power Consumption (C/H) kW 8.0 / 7.7 10.1 / 10.1 Running Current (C/H) Amps 12.3 / 11.7 15.7 / 15.0...
Page 61
TOSHIBA 1. Specifications MULTI CONTROLLERS Model RBM-Y1032E-E RBM-Y1042E-E Number of Branches Gas Pipe (Inlet) Inch 1 1/8 1 1/8 Liquid Pipe (Inlet) Inch Branch Pipes (Gas) Inch 3/4 x 3 3/4 x 4 Branch Pipes (Liquid) Inch 3/8 x 3...
TOSHIBA 2. Basic Permutations of Indoor to Outdoor Units The indoor units are given a code number according to their capacity rank - see below Model Number Code Number RAV103 RAV132/133 RAV453/160/1/2/3 RAV202/3 RAV713/260/1/2/3 RAV1003/360/1/2/3 RAV1253/460/1/2/3 Multiple indoor units may be connected to one outdoor unit, providing the total indoor code does not exceed the outdoor unit code number.
Page 63
TOSHIBA CONSTRUCTION VIEWS MAR-M81HTM8E-E MAR-M101FHTM8E-E 98 mm 790 mm 824 mm 90 mm 750 mm 610 mm 375 mm 130 mm 160 mm AUGUST 1997 Page 6...
Page 64
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1032E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more...
Page 65
TOSHIBA DIMENSIONAL DRAWINGS RBM-Y1042E-E Oval holefor hanging bolt Slit for hanging bolt 15 mm 560 mm 590 mm 90 mm 170 mm 170 mm 490 mm 90 mm Electric Parts Box 500 mm 100 mm 50 mm or more or more...
Page 66
TOSHIBA 4. Schematic Wiring Diagrams Outdoor Unit Reactor Giant Electric Starter Contactor Transistor Rectifier Smoothing Circuit 52C1 λ 2200 F/400v x 2 47k Ω /20W x 2 ℜ Noise Filter Contactor 52C2 U V W 1 2 3 4 ℜ...
Page 68
TOSHIBA 5. Schematic Refrigeration Diagram Outdoor Unit INVERTER COMPRESSOR H.P. SWITCH EXPANSION SERVICE VALVE PRESSURE VALVE ThD1 SENSOR PRESSURE INVERTER SWITCH COMPRESSOR DRIER LIQUID TANK HEAT CHECK VALVE EXCHANGER D.O.L. COMPRESSOR ThD2 HIGH PRESSURE RELEASE 4-WAY VALVE D.O.L. SERVICE H.P.SWITCH...
Page 69
TOSHIBA 5. Schematic Refrigeration Diagram Multi Controller INDOOR UNIT EXPANSION VALVE PMV(A) STRAINER BRANCH A CHECK VALVE EXPANSION VALVE PMV(B) LIQUID PIPE STRAINER STRAINER BRANCH B CHECK VALVE EXPANSION VALVE PMV(C) STRAINER BRANCH C CHECK VALVE EXPANSION VALVE PMV(D) STRAINER...
Page 70
TOSHIBA 6. Fault Code and Display Information Fault Codes Before reading the fault codes do not turn the power off as doing so will wipe the diagnostic memory. Caution must be taken when removing the access covers as high voltages are present.
Page 71
TOSHIBA 6. Fault Code and Display Information Display switch information Multicontroller Switch position Information System Communication Fault Codes Level of Demand Oil Retrieval, Superheat, Defrost Operating Mode Restart Timer Circuit Test (commissioning only) PMV(A) Position PMV(B) Position PMV(C) Position PMV(D) Position...
Page 72
TOSHIBA 6. Fault Code and Display Information Multi Controller Display Switch Information Switch Indicates LD 1 LD 2 Pos. |_| | |_ _ |_| | |_ _ |_| | |_ _ |_| | |_ _ Serial From B To B...
Page 73
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information The operating status of the outdoor unit and fault diagnosis can be made using both the display selector switch (on the interface pcb) and the eight red light emitting diodes on the interface printed circuit board.
Page 74
TOSHIBA 6. Fault Code and Display Information Outdoor Unit Display Switch Information cont. d. Display switch set to position “3” identifies a fault condition in the outdoor unit. Details are in the fault code chart on page 13 e. Display switch set to positions “4, 5, 6 & 7” identifies the indoor unit capacity code for each branch.
Page 75
TOSHIBA 7. Circuit Test Procedure These systems have a feature which enables them to check that the wiring and piping connections are aligned with each other. This is carried out by allowing refigerant flow to one indoor unit at a time and monitoring that indoor unit’s coil sensor for a corresponding drop in temperature.