Table 2-4: Floor Load Rating and Clearances: Two Racks
Floor Load Rating
kg/m
500 (102.4)
450 (92.2)
400 (81.9)
350 (71.7)
300 (61.4)
•
NOTE: For safe and efficient maintenance operations, clearance (c) should
be made as large as possible. Actual clearances for installation should be
determined after consulting with the site/facilities manager, as the
clearances can vary, depending on building conditions.
Customer-Supplied Rack
This section lists the physical specifications and requirements for installing
the Universal Storage Platform VM in a customer-supplied rack.
Rack Dimensions
•
Height: 1900–2000 mm
•
Width: 600–610 mm
•
Depth: Minimum of 1000 mm
Minimum U Height
The minimum height is 36U.
While your initial system configuration may not require 36U, this amount of
space is required for a full configuration. Initially allocating this amount of
space minimizes the time required to reposition equipment in the future.
Rail Kits
Figure 2-6 on page 2-13
the 3U rail kits shown in blue and the 2U rail kits shown in orange.
7 on page 2-14
Backup Chassis obtains its power from the Control Frame and must be
installed directly above the Control Frame.
2–12
Hitachi Universal Storage Platform VM Installation Planning Guide
2
2
(lb./ft.
)
C=0
0.2
0.2
0.2
0.4
0.8
shows the general positioning of the rail kits with
shows the rail kit alignment and spacing. The SVP/Battery
Installation Requirements
Required Clearance (a+b) m
Clearance (c) m
C=0.2
C=0.4
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.2
0.3
0.2
0.2
0.6
0.5
0.4
C=0.6
C=1.0
0.2
0.2
0.2
0.2
0.2
Figure 2-