Whirlpool Gold WGFM195 Installation Instructions Manual page 36

Gold gas-fired warm air furnace
Hide thumbs Also See for Gold WGFM195:
Table of Contents

Advertisement

Gas Control Valve—White-Rodgers 36G54 Connected to
Manometer
A
K
L
A. Open to atmosphere
B. Manometer hose
C. Outlet pressure boss
D. High-fire regulator adjust
E. Regulator vent
F. Low-fire regulator adjust
Gas Control Valve—Honeywell VR9205 2-Stage
F
A. Regulator vent
B. High-fire regulator adjust
C. Outlet
Gas Control Valve—Honeywell VR9205 Connected to
Manometer
B
A
i
H
A. Open to atmosphere
B. Manometer hose
C. Common terminal (C)
D. High-fire coil terminal (HI)
36
B
C
D
J
I
H
G
G. Coaxial coil terminal (M)
H. Common terminal (C)
I. High-fire coil terminal (HI)
J. On/Off selector switch
K. Inlet pressure boss
L. Manometer
A
B
C
D
E
D. Low-fire regulator adjust
E. On/Off selector switch
F. Inlet
C
D
E
F
G
E. Low-fire coil terminal (LO)
F. ¹⁄₈ " NPT inlet pressure tap
G. ¹⁄₈ " NPT outlet pressure tap
H. Manometer
1. Turn off the gas supply to the furnace at the manual gas
shutoff valve external to the furnace.
2. Disconnect all electrical power to the system.
3. Connect a calibrated water manometer (or appropriate gas
pressure gauge) at either the gas control valve inlet pressure
boss or the gas piping drip leg. See "Gas Control Valve—
Honeywell VR9205 Connected to Manometer" or "Gas
Control Valve—White-Rodgers 36G54 Connected to
E
Manometer" illustration for location of inlet pressure boss/
tap.
NOTE: If you are measuring the gas pressure at the drip leg or on
the Honeywell VR9205 gas control valve, a field-supplied hose
barb fitting must be installed prior to making the hose
F
connection. If using the inlet pressure boss on the White-Rodgers
36G54 gas control valve, then use the 36G Valve Pressure Check
Kit, Part Number 0151K00000S.
4. Turn on the gas supply and operate the furnace and all other
gas consuming appliances on the same gas supply line.
5. Measure the furnace gas supply pressure with burners firing.
NOTE: Supply pressure must be within the range specified in the
Inlet Gas Supply Pressure chart.
Inlet Gas Supply Pressure
Natural Gas
Propane Gas
If the supply pressure differs from chart, make the necessary
adjustments to the pressure regulator, gas piping size, etc., and/
or consult with local gas utility.
6. Turn off the gas supply to the furnace at the manual shutoff
valve.
7. Disconnect the manometer.
8. Reinstall plug before turning on gas supply to furnace.
9. Turn off any unnecessary gas appliances that were turned on
in Step 4.
Measuring Inlet Gas Pressure—Alternate Method
A. Gas supply line
B. Gas shutoff valve
C. Gas supply line to furnace
D. Open to atmosphere
Minimum: 5.0" W.C. Maximum: 10.0" W.C.
Minimum: 11.0" W.C. Maximum: 13.0" W.C.
A
B
C
D
G
F
E
E. Manometer
F. Manometer hose
G. Dripleg cap with fitting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gold wfd195Gold wfm195Wpio-299nGold wfd193

Table of Contents