Setting Of System Connection; List Of Setting Items - Panasonic FP7 CPU Unit User Manual

Lan port communication
Table of Contents

Advertisement

3.5 Setting of System Connection

3.5.1 List of Setting Items

System connection is used when using a programming tool via LAN port.
 List of setting items
Setting item
Operation Mode Setting
Specifying use of
connection
MEWTOCOL
communication type
Open method
(server/client)
Open method
(auto/manual)
Communication method
Source node port No.
Partner node port No.
Connection closing time
Partner node - Setting
method
Partner node IP address and
name
Default
MEWTOCOL-COM
Yes
Do not connect with FP2
ET-LAN
Server connection
(unspecified partner)
Auto OPEN
TCP / IP
Connection 01: 32769
Connection 02: 32770
Connection 03: 32771
Connection 04: 32772
Connection 01: 32769
Connection 02: 32770
Connection 03: 32771
Connection 04: 32772
Connection 01: 6000
Connection 02: 360000
Connection 03: 360000
Connection 04: 360000
Specification using IP
address (IPv4)
0.0.0.0
3.5 Setting of System Connection
System Connection - Setting method
Select the operation mode MEWTOCOL-COM.
Specify whether system connection is to be used.
Select "Do not connect with FP2 ET-LAN".
Select connection function settings (server
connection (unspecified partner).
Select the connection open method (auto/manual).
Select "Auto OPEN".
Select the communication protocol (TCP/IP).
Specify the source node (sender) port number.
Specify the partner node (receiver) port number.
This needs not to be set if the partner node is not
specified.
Setting unit:
Input the no-connection communication monitoring
time. Connection is automatically cut off when no-
connection communication exceeds the specified
time.
Select the setting for partner node (IP address).
This needs not to be set if the partner node is not
specified.
Specify the setting for partner node (IP address /
host name). This needs not to be set if the partner
node is not specified.
3-7