MODBUS TCP Master/Slave Communication

6.1 MODBUS TCP Format

6.1.1 MODBUS TCP

 Data structure for the MODBUS TCP format
• In MODBUS TCP, an MBAP header is attached to the function codes and data used in
MODBUS-RTU.
MODBUS TCP format
MBAP header part
 Data contents
Fields
Transaction Identifier
Protocol Identifier
MBAP
Header
Length
Unit Identifier
Function code
Data
KEY POINTS
Function codes and data parts for MODBUS TCP are the same as those for
MODBUS-RTU. Note that, however, CRC check codes contained in the
MODBUS-RTU format are not included.
REFERENCE
For detailed specifications concerning MODBUS, please see the website
http://www.modbus.org/
6-2
MBAP Header
7 bytes
Transaction
Protocol
Identifier
Identifier
2 bytes
2 bytes
Field name
Transaction identifier
Protocol identifier
Length
Unit identifier
Function code
Data
.
Function
Code
1 byte
Unit
Length
Identifier
2 bytes
1 byte
Description
"00H" is entered.
"00H" is entered.
The length of the subsequent sending/receiving
message is entered.
Station no. of the unit is entered. 0 - 247
The same function name as that of MODBUS-
RTU is entered.
Data that correspond to the function code are
entered.
Data
n bytes