Gt21 - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

3.1.3

GT21

Item
Operating ambient temperature
*1
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistant
Operating atmosphere
*3
Operating altitude
Installation location
*4
Overvoltage category
*5
Pollution degree
Cooling method
Grounding
*1
*2
*3
*4
*5
3 - 4
3.1 General Specifications
0°C to 55°C (Horizontal installation), 0°C to 50°C (Vertical installation)
Compliant with
intermittent
JIS B3502 and
IEC61131-2
continuous
Compliant with JIS B3502 and IEC61131-2 (147 m/s
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust,
The operating ambient temperature indicates the temperature inside the enclosure of the control panel to which the GOT is
installed.
If the ambient temperature exceeds 40 °C, the absolute humidity must not exceed 90% at 40 °C.
Do not use or store the GOT under a pressure higher than the atmospheric pressure at altitude 0 m.
Doing so may cause a malfunction.
Air purging by applying pressure to the control panel may create clearance between the surface sheet and the touch panel. This
may cause the touch panel to be not sensitive enough or the sheet to come off.
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical
power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V.
This indicates the occurrence rate of conductive material in an environment where a device is used. Pollution degree 2 indicates
an environment where only non-conductive pollution occurs normally and a temporary conductivity caused by condensation shall
be expected depending on the conditions.
Specifications
-20°C to 60°C
10% RH to 90% RH, non-condensing
10% RH to 90% RH, non-condensing
Frequency
Under
5 to 8.4 Hz
8.4 to 150 Hz
vibration
Under
5 to 8.4 Hz
8.4 to 150 Hz
vibration
and direct sunlight (as well as at storage)
2000 m or less
Inside control panel
II or less
2 or less
Self-cooling
Grounding with a ground resistance of 100 Ω or less.
If impossible, connect the ground cable to the control panel.
*2
*2
Acceleration
Half amplitude
-
3.5 mm
2
-
9.8 m/s
-
1.75 mm
2
4.9 m/s
2
(15G), 3 times in each X, Y, or Z direction)
Sweep count
10 times in
each X, Y, or Z
direction
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents