Preparing for Installation
To comply with the Telcordia GR-1089 Network Equipment Building Systems (NEBS) standard for
Caution
electromagnetic compatibility and safety, connect the Ethernet cables only to intrabuilding or
nonexposed wiring or cabling.
To comply with the Telcordia GR-1089 NEBS standard, PoE or non-PoE 10/100/1000 Ethernet port
Caution
cables that exit from either the left or right side of the switch should be routed and tied to the nearest
rack metal.
Note
The grounding architecture of this product is DC-isolated (DC-I)

Installation Guidelines

Before installing the switch, verify that these guidelines are met:
Catalyst 3750-X and 3560-X Switch Hardware Installation Guide
2-4
Clearance to front and rear panels is such that
Front-panel indicators can be easily read.
Access to ports is sufficient for unrestricted cabling.
AC power cord can reach from the AC power outlet to the connector on the switch rear panel.
The SFP or SFP+ module minimum bend radius and connector length is met. See the SFP or
SFP+ module documentation for more information.
For switches with the optional 1100-W power-supply module (C3KX-PWR-1100WAC=), first
rack-mount the switch before installing the power-supply module.
Make sure power-supply modules and fan modules are securely inserted in the chassis before
moving the switch.
When connecting or disconnecting the power cord on a switch that is installed above or below a
1100-W power supply-equipped switch, you might need to remove the module from the switch to
access the power cord.
Cabling is away from sources of electrical noise, such as radios, power lines, and fluorescent
lighting fixtures. Make sure that the cabling is safely away from other devices that might damage
the cables.
For copper connections on Ethernet ports, cable lengths from the switch to connected devices can
be up to 328 feet (100 meters).
For cable requirements for SFP+ module connections, see the
section on page
B-5. Each port must match the wave-length specifications on the other end of the
cable, and the cable must not exceed the minimum cable length.
Operating environment is within the ranges listed in
Airflow around the switch and through the vents is unrestricted.
Chapter 2
"Cable and Adapter Specifications"
Appendix A, "Technical Specifications."