Electrolux EN19WI30LS Installation Manual page 17

Condensing tankless gas water heater
Hide thumbs Also See for EN19WI30LS:
Table of Contents

Advertisement

Vent Pipe Installation
Horizontal Vent Termination- PVC/CPVC Materials Only
5.9"
Exhaust
Exterior View
Interior View
Exhaust
Intake
Interior View
Exterior View
Exhaust
Interior View
Exterior View
WARNING
If the distance between the air inlet and exhaust vent terminations is too short, the water heater
will draw in the exhaust gases through the intake. There is a risk of inadequate combustion air
for the water heater, increasing Carbon Monoxide (CO) emissions and noise due to vibration.
• Termination elbows must be oriented vertically, pointing directly downward. Attempts to prevent
exhaust air from entering the air inlet by angling termination elbows in directions other than
directly downward will increase the risk of freezing.
• Reversing the air intake and exhaust pipes is not allowed.
Carbon Monoxide (CO) emissions and noise due to vibration will increase.
Intake
2ft. Min
3" Min
Exhaust
1ft. Min
5.9"
3" Min
Exhaust
Intake
5.9"
3" Min
Intake and exhaust should face the same direction.
Intake and exhaust should keep the same
pressure zone.
Insert the bird screen.
90° elbow vertical setting (downward).
Ensure at least 3ft (0.9m) or more distance between
the near edge of the air intake pipe or exhaust pipe
to the inside corner of a wall.
Ensure at least 2ft (0.6m) or more distance between
intake pipe and exhaust pipe.
The distance is measured at inside of pipe to inner
dimension.
Intake and exhaust should face the same direction.
Intake and exhaust should keep the same
pressure zone.
Insert the bird screen.
90° elbow vertical setting (downward).
1ft. Min
Ensure at least 3ft (0.9m) or more distance between
edge of air intake pipe or exhaust pipe and corner wall.
Intake
Upper side is exhaust, lower side is intake.
The reverse connection is not allowed.
Ensure at least 1ft (0.3m) or more distance between
intake pipe and exhaust pipe.
The distance is measured at the outlets of
intake port (terminal) and exhaust port (terminal).
Intake and exhaust should face the same direction.
Intake and exhaust should keep the same
pressure zone.
Insert the bird screen.
Intake
90° elbow vertical setting (downward).
Ensure at least 3ft (0.9m) or more distance between
edge of air intake pipe or exhaust pipe and corner wall.
1ft. Min
The side distant from wall is intake, the side near the
wall is exhaust.
The reverse connection is not allowed.
Ensure at least 1ft (0.3m) or more distance between
intake pipe and exhaust pipe.
The distance is measured at inside of pipe to inner
dimension.
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ep19wi30ls

Table of Contents