10. Remove the lock and set the MBP's manual Bypass switch to the UPS
11. On the UPS, select Control > Go back normal to put the UPS into Online
12. Check that the UPS is in Online mode by checking its display panel. The load

Recycling the used equipment

Contact your local recycling or hazardous waste center for information on proper
disposal of the used equipment. Refer to the Lenovo Systems Environmental Notices
and User Guide on the Lenovo Documentation CD for more information.
Important:
4. Verify that all wiring is correct. Then, push the conduits into the terminal
block cover until they lock in place. Attach the access cover to the terminal
block cover.
5. On the MBP, unlock the Normal AC source switch
source switch
(3Phase model only), and set them to the 1 (on) position.
6. Wait for the UPS to start functioning.
The display panel illuminates and displays the standby symbol:
7. Press the power (
The UPS goes into online mode:
8. Select Control > Go to Bypass
The UPS goes into bypass mode:
9. Verify that the UPS mode green light on the MBP is on, indicating that the
UPS output power is available to the MBP. Do not continue to the next step if
the UPS mode green light on the MBP is off. If the green light is off and the
manual rotary switch is moved to the UPS position, the load will lose power.
position.
The Bypass mode red light on the MBP goes off, indicating that the load is
now powered by the UPS.
mode.
is now protected by the UPS.
) button to turn on the UPS.
and the Bypass AC
Chapter 7. UPS maintenance