Hotswap Mbp Specifications - Lenovo RT8.0kVA Installation And User Manual

6u rack or tower ups
Hide thumbs Also See for RT8.0kVA:
Table of Contents

Advertisement

HotSwap MBP specifications

Table 17. Environmental and safety standards (continued)
Storage temperature
Transit temperature
Relative humidity
Operating altitude
Transit altitude
Audible noise
Table 18. Battery
Rating
Fuse
Type
Monitoring
Battery port
EBM battery cable length
Table 19. Communication options
Communication bay
Compatible connectivity cards
Communication ports
Relay output contacts
Remote On/Off
Remote Power Off
8/11k VA 1Phase
Terminal blocks
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
-25 to 55°C (-13 to 130°F)
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10%
derating per 1000m
Up to 10,000 meters (32,808 ft) above sea level
< 48 dBA at 1 meter typical for 6-8kVA models
< 50 dBA at 1 meter typical for 11kVA model
EBMs
240Vdc 20 x 12V, 9Ah
80A
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30°C (86°F).
Advanced monitoring for earlier failure detection and
warning
External three-pole SBS75G White connector on Power
Module for connecting to EBM
40cm (15.7in)
(1) available independent communication bay for
connectivity cards
UPS Network Management Card (included)
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
(4) relay outputs (normally open or normally closed)
2 pins jumper (normally open)
3 pins jumper (normally open or normally closed)
MBP11Ki
Input
Input Bypass
8/11k VA 3Phase
Appendix A. Specifications
65

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rt11.0va

Table of Contents