Appendix A. UPS model specifications
The Lenovo 3U Rack or Tower UPS, model 5594-5KX and model 5594-6KX, is a
single-phase UPS unit.
© Copyright Lenovo 2015
Table 4. Power Module model list
Model
5594-5KX
5594-6KX
Table 5. EBM model list
Model
Configuration
5594-6BX
Rack / Tower
Table 6. Electrical input
Nominal frequency
Frequency range
Bypass voltage range
Noise filtering
Table 7. Electrical input (models)
Default input
Model
(Voltage/Current)
5594-5KX
208V / 23.3A
5594-6KX
208V / 24.8A
Table 8. Electrical input connections
Model
5594-5KX
5594-6KX
Table 9. Electrical output
All models
Normal mode
Voltage regulation
±1%
Power Ratings
5000VA / 4500W at 200V, 208V, 220V, 230V, and 240V output
5200VA / 4600W at 200V output
5400VA / 4800W at 208V output
5700VA / 5100W at 220V output
6000VA / 5300W at 230V output
6000VA / 5400W at 240V output
EBM voltage
180Vdc
50/60Hz auto-sensing
50Hz : 40-60Hz before transfer to battery
60Hz : 50-70Hz before transfer to battery
-20% / +15% of nominal value (default)
MOV for normal and common mode noise
Selectable input
Voltage range
200V, 208V, 220V,
230V, 240V
Input connection
Selectable input cord
Hardwired
For power ratings
5000-6000VA
Voltage
at 100% Load
176-276V
Battery mode
±1%