Lenovo 5594-6KX Installation And User Manual page 70

Hide thumbs Also See for 5594-6KX:
Table of Contents

Advertisement

52
Installation and User's Guide
Table 14. Environmental and safety standards (continued)
EMC (Immunity)
Agency markings
Operating temperature
Storage temperature
Transit temperature
Relative humidity
Operating altitude
Transit altitude
Audible noise
Table 15. Battery
Rack / Tower
configuration
Type
Monitoring
Battery port
EBM battery cable
length
Table 16. Communication options
Communication bay
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
CE / cULus / NOM
0 to 40°C (32 to 104°F) in Online mode, with linear derating for
altitude
Note: Thermal protection switches load to Bypass in case of
overheating.
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
-25 to 55°C (-13 to 130°F)
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10% derating
per 1000m
Up to 10,000 meters (32,808 ft) above sea level
< 45 dBA at 1 meter typical
Internal batteries
5000/6000VA: 180Vdc
Sealed, maintenance-free, valve-regulated, lead-acid, with
minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30°C.
Advanced monitoring for earlier failure detection and warning
External three-pole SBS75G Black connector on UPS for
connecting to EBM
40cm (15.7in)
(1) available independent communication bay for connectivity
cards
EBMs
5594-6BX: 180Vdc

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5594-5kx5594-6bx

Table of Contents