50
Installation and User's Guide
Table 9. Electrical output (continued)
All models
Normal mode
Efficiency
> 98% (High Efficiency mode)
> 93%
Frequency regulation
Sync with line ±5% of nominal line
frequency (outside this range: ±0.5%
of auto-selected nominal frequency)
Frequency
50 or 60Hz, autosensing or configurable as a frequency converter
Output overload
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 500ms
Output overload
100-125% : no alarm
(Bypass mode)
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Voltage waveform
Sinewave
Harmonic distortion
< 2% THDV on linear load
< 5% THDV on non-linear load
Transfer time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Power factor
0.9
Load crest ratio
3 to 1
Table 10. Electrical output connections
Model
5594-5KX
5594-6KX
Table 11. AC input and output
AC Input power
Output connection
Hardwired
(2) IEC 16A
(4) IEC 10A group 1
(4) IEC 10A group 2
5594-5KX
200-240VAC, 50/60Hz, 1ph,
25A max
Battery mode
> 91%
±0.5% of auto-selected
nominal frequency
Output cable
(2) IEC 10A
5594-6KX
200-240VAC, 50/60Hz, 1ph,
30A max

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5594-5kx5594-6bx

Table of Contents