Submenu
Battery settings
Automatic battery
test
Low battery warning [0%] ... [100%]
Restart battery level
Battery charge mode
External battery
Deep discharge
protection
Available settings
Default settings
In constant charge
[Every ABM cycle]
mode:
[No test] [Every day]
[Every week] [Every
month]
In ABM cycling
mode:
[No test] [Every ABM
cycle]
[20%]
The alarm triggers
when the set
percentage of
battery-pack capacity
is reached during
back-up time.
[0%] ... [100%]
[0%]
If set, automatic
restart will occur
only when
percentage of battery
charge is reached.
[ABM cycling]
[ABM cycling]
[Constant charge]
[Auto detection]
[Auto detection]
Using standard EBM,
[Manual EBM set.]
UPS detects
[Manual battery set.]
automatically the
[No battery]
number of EBM
connected
[Yes] [No]
[Yes]
If set to Yes, the UPS
automatically
prevents batteries
from deep discharge
by adapting end of
back-up time voltage
threshold. Warranty
void if set to No.