Technical Specifications: 200V/230V Models - Lenovo RT1.5kVA Installation And User Manual

2u rack or tower ups
Hide thumbs Also See for RT1.5kVA:
Table of Contents

Advertisement

When the appliance is used in the EU, use an external circuit breaker in front of
line with rating 16 A, 250 V which is IEC/EN 60898-1 standard compliant.
When the appliance is used in American area, use an external circuit breaker in
front of line with rating 20 A, 250 V.
This product is designed for IT power distribution systems.

Technical specifications: 200V/230V models

The Lenovo 2U Rack or Tower UPS, 200V model and 230V model, is a single-phase
UPS unit.
42
Installation and User's Guide
Environment
(1) Adjustable to 100 V (17 % derating at 100 V on 1.5 kV A / 3 kV A, 32 % derating at 100 V on 2.2 kV A) 120/125 V.
(2) 5594-2BX: 2 strings, each 4 x 12 V / 9 Ah.
(3) 5594-3BX: 2 strings, each 6 x 12 V / 9 Ah.
Output Power
AC Input power
200-240VAC,
50/60Hz, 1ph, 10A
max
5594-1AX
5594-2AX
Operating temperature: 0 to +40 °C (32 to 104 °F)
Storage temperature: -15 to +50 °C (5 to 122 °F)
Relative humidity: 20 to 90 % (without condensation)
Noise level: < 45 dBA
5594-1KX
5594-2KX
1500 VA
2200 VA
1350 W
1980 W
200-240VAC,
50/60Hz, 1ph, 16A
max
5594-3AX
Noise level: < 50 dBA
5594-3KX
3000 VA
2700 W
200-240VAC,
50/60Hz, 1ph, 16A
max