Mitsubishi Electric AG-150A Instruction Book page 17

Air-conditioner network system
Hide thumbs Also See for AG-150A:
Table of Contents

Advertisement

4-2-4-1 Settings for when the AG-150A is connected to a dedicated LAN
(1) Enter the AG-150A IP address in the [IP Address] field. If the LAN wiring has been newly set up, allocate IP
addresses to the AG-150A units in a sequential order starting with [192.168.1.1]. For example the first
AG-150A unit will receive an IP address of [192.168.1.1], the second AG-150A unit will receive an IP
address of [192.168.1.2] and so on.
The Web Monitor PC that monitors and sets AG-150A will also require network addresses consistent with
the rest of the LAN.
Note: When using a AG-150A dedicated LAN, it is recommended to set the IP address as follows.
AG-150A: Between [192.168.1.1] and [192.168.1.40] Web Monitor PC: Between [192.168.1.101] and [192.168.1.150]
[Example of IP address setting]
AG-150A No. 1
192.168.1.1
(2) Enter the AG-150A subnet mask in the [Subnet Mask] field. Normally, you should enter [255.255.255.0].
(3) When monitoring remotely or sending error mail via a dial-up router, enter the router IP address in the [Gateway]
field.
Leave the gateway address blank when not connecting via a dial-up router.
[Example of a Remote Monitoring System]
AG-150A
IP Address
:192.168.1.1
Subnet Mask
:255.255.255.0
G/W Address
:192.168.1.254
100BASE-TX LAN straight cable
AG-150A No. 2
192.168.1.2
Note: Some hubs have a dedicated port for connection with another hub.
Connect the AG-150A and Web Monitor PC to the normal ports.
Dial-up router
IP: 192.168.1.254
Web Monitor PC
IP Address
Subnet Mask
G/W Address
Note: It is recommended to set the dial-up router IP address to [192.168.1.254]. Refer to the dial-up
router instruction manual for details of how to set the IP address.
Note: It is necessary to connect a modem (analog type or ISDN type) between the dial-up router
and telephone line when using a dial-up router that does not have a built-in modem.
Hub
AG-150A No. 3
192.168.1.3
Telecommunication Network
:192.168.1.101
:255.255.255.0
:Blank
16
Web Monitor PC
192.168.1.101
Dial-up router, cellular phone etc.
Web Monitor PC