3 Performing Operations

Text below explains how to connect to the AG-150A and how to make various settings for the AG-150A.
Note: If the AG-150A is restarted due to a power interruption etc., wait until the screen on the AG-150A main unit displays the
normal operation screen (it takes several minutes before the normal operation screen is displayed) before using a web
browser to access the AG-150A. If access is attempted while the AG-150A is still starting up, the most recent data might
not be displayed or communication errors could occur.
Note: Default IP address of AG-150A is "192.168.1.1". (Factory setting)

3-1 Logging in on the AG-150A

3-1-1 Logging in on the AG-150A
(1) Enter the web page address in the address field of the web
browser as follows:
http:// [IP address of the AG-150A]/g-50
Press the [Enter] key on the keyboard. A screen appears for login.
Note: For example, type "http://192.168.1.1/g-50/administrator.html" if the
AG-150A IP address is [192.168.1.1].
(2) To make connection easier for the next time, click the web
browser menu item [Favorites], click [Add to Favorites], then add
the address to the Favorites folder. Once this address is added to
the Favorites folder, it is not necessary to input the address of (1).
Simply select it from the Favorites folder and the AG-150A page
will appear.
(3) Enter the user name and the password in the login screen, and click the [Login] button. A screen will
appear in which various setting are made. An explanation on how to perform operations begins from the
next page.
The table below shows the default user names and passwords for maintenance users and building
managers as well as available functions.
User
Maintenance
user
Building
manager
Note: The user name and the password for building manager are the same as those of the building manager of the Web for
monitoring/operation.
Note: Maintenance users can make available to the administrator only the information necessary for normal operations (group
name setting etc.)
Note: It is recommended to change the user name and password so users other than the manager are not permitted to change
the settings.
Note: The Web page is displayed in the same language as the computer uses and it is also possible to display the Web page in
other languages by entering the following Web page addresses.
English
German
French
Spanish
Italian
Russian
Chinese
Portuguese :http://[The IP address of AG-150A]/g-50/pt/administrator.html
Japanese
/administrator.html
Default
Default
user name
password
initial
init
administrator
admin
:http://[The IP address of AG-150A]/g-50/en/administrator.html
:http://[The IP address of AG-150A]/g-50/de/administrator.html
:http://[The IP address of AG-150A]/g-50/fr/administrator.html
:http://[The IP address of AG-150A]/g-50/es/administrator.html
:http://[The IP address of AG-150A]/g-50/it/administrator.html
:http://[The IP address of AG-150A]/g-50/ru/administrator.html
:http://[The IP address of AG-150A]/g-50/zh/administrator.html
:http://[The IP address of AG-150A]/g-50/ja/administrator.html
Available functions
Date and Time, Basic System, Groups, Interlocked
Initial settings
LOSSNAY, Blocks
Functions 1
E-Mail, Peak cut, Measurement
Set Temperature Range Limit, Night Mode
Functions 2
Schedule, System-changeover
Interlock control based on outside temperature,
Functions 3
Setback control
Interlock control
User Settings
User Settings
Out of the functions listed above, the items to which access rights
have been given on the user settings screen are available.