Burnout Alarm Output - Panasonic KT9 Instruction Manual

Hide thumbs Also See for KT9:
Table of Contents

Advertisement

• ON/OFF action: When OUT1 proportional band is set to 0
OUT1 proportional band (P)
Integral time (I)
Derivative time (D)
OUT1 proportional cycle : 1 to 120sec (Not available for DC current output type)
ARW
OUT1 hysteresis
SV1/SV2 external selection: SV1 and SV2 can be selected by external contact.
Contact open between terminals 14 and 17 : SV1
Contact closed between terminals 14 and 17: SV2
Contact current: 6mA
Supply voltage
Allowable voltage fluctuation range
Ambient temperature: 0 to 50
Ambient humidity
Power consumption : Approx. 8VA
Circuit insulation configuration
Ground
1
2
Power
source
3
4
5
OUT1
A
6
7
8
9
OUT2 or Heater

burnout alarm output

10
• When OUT1 is non-contact voltage or DC current output type and OUT2 is Non-
contact voltage or DC current output type, A is not insulated from B.
• When OUT1 is non-contact voltage or DC current output type, A is not insulated from
C, and A is not insulated from D.
When OUT2 is non-contact voltage or DC current output type, B is not insulated from
C, and B is not insulated from D.
Insulation resistance
10M
or more, at 500V DC for other combinations except the above mentioned
Thermocouple: 0 to 1000
RTD: 0.0 to 999.9
DC current, voltage: 0.0 to 100.0%
(ON/OFF action when set to 0 ( ), 0.0 ( ) or 0.0%)
: 0 to 1000sec (Off when set to 0)
: 0 to 300sec (Off when set to 0)
: 0 to 100%
: 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
100 to 240V AC : 85 to 264V AC
24V AC/DC
(32 to 122 )
: 35 to 85%RH (no condensation)
A2 output or Heater
Insulated
B
(0.0 to 999.9 )
of the decimal point follows the selection)
: 20 to 28V AC/DC
12
13
15
CT input
SV2
16
18
19
20
39
(0 to 2000 )
( )
11
14
14
D
C
17
17