Dielectric strength
Between input terminal and ground terminal, 1.5kV AC for 1 minute
Between input terminal and power terminal,
Between output terminal and ground terminal, 1.5kV AC for 1 minute
Between output terminal and power terminal, 1.5kV AC for 1 minute
Between power terminal and ground terminal, 1.5kV AC for 1 minute
Weight
External dimension: 96 x 96 x 98.5mm (W x H x D)
Material
Color
Attached function
[Sensor correction function]
[Set value lock function]
[Input abnormality indication]
Output
Contents and
selection
when input
Indication
abnormal
Overscale
Measured value
has exceeded
Indication range
high limit value.
"
Underscale
Measured value
has dropped
below Indication
range low limit
value.
"
" flashes.
Only for DC input and DC current output type, [Output status selection when input
abnormal] is available. For other inputs and outputs except for DC input and DC
current output, the output status will be the same one as when OFF is selected
during [Output status selection when input abnormal].
For manual control, the preset manipulated variable (MV) is outputted.
(*): Outputs a value between OFF (4mA) and ON (20mA) or between OUT1 (OUT2)
low limit value and OUT1 (OUT2) high limit value, depending on deviation.
Thermocouple, RTD input:

Input

K,T
Pt100
JPt100
For the thermocouple inputs other than the above, both the Indication range and
Control range are: Input range low limit value – 50
: Approx. 370g
: Case, Flame-resistant resin
: Case, Ash gray
Direct action
ON (20mA) or
OUT1 high
limit value (*)
OFF (4mA) or
OUT1 low
" flashes.
limit value
OFF (4mA) or
OUT1 low
limit value
Input range
–199.9 to 400.0
–199.9 to 750.0
–199.9 to 850.0
–200 to 850
–199.9 to 999.9
–300 to 1500
–199.9 to 500.0
–200 to 500
–199.9 to 900.0
–300 to 900
limit value + 50
1.5kV AC for 1 minute
Output status
OUT1
Reverse
action
OFF (4mA) or
OUT1 low
limit value
ON (20mA) or
OUT1 high
limit value (*)
OFF (4mA) or
OUT1 low
limit value
Indication range
–199.9 to 450.0
–199.9 to 850.0
–199.9 to 900.0
–210 to 900
–199.9 to 999.9
–318 to 1600
–199.9 to 550.0
–207 to 550
–199.9 to 999.9
–312 to 1000
(100 ) to Input range high
(100 )
40
OUT2
Reverse
Direct action
ON (20mA) or
OUT2 high
OFF (4mA) or
limit value(*)
OUT2 low
OFF (4mA) or
limit value
OUT2 low
limit value
ON (20mA) or
OUT2 high
limit value (*)
OFF (4mA) or
OUT2 low
OFF (4mA) or
limit value
OUT2 low
limit value
Control range
–205.0 to 450.0
–209.0 to 850.0
–210.0 to 900.0
–210 to 900
–211.0 to 1099.9
–318 to 1600
–206.0 to 550.0
–207 to 550
–211.0 to 999.9
–312 to 1000
action