Figure 4.5 Psychrometric Chart Applicable To Changing The Room Temperature; Table 4.2 Temperature And Humidity Recommendations (Changing The Room Temperature) - Fujitsu M10 Series Installation Planning Manual

Hide thumbs Also See for M10 Series:
Table of Contents

Advertisement

Table 4.2 Temperature and humidity recommendations (changing the room
temperature)
Near the underfloor air
Air conditioning
setup
Temperature
C
Direct blow or
duct blow
181 C 642 F 655%
Underfloor
ventilation
191 C 662 F 625%
20 1 C 682 F 585%
181 C 642 F 655%
Combined use of
191 C 662 F 625%
direct blowing or
duct blowing
20 1 C 68 2 F 585%
and underfloor
ventilation
Figure 4.5
temperature, relative humidity, and absolute temperature.

Figure 4.5 Psychrometric chart applicable to changing the room temperature

C120-H007-08EN
outlet
Humidity
F
%
is an air-line diagram depicting the relationships between the dry-bulb
Detection and regulation
point
Temperature
C
F
Setting:
Setting:
Between 21
Between 70
and 26 Width
and 79 Width
of variation:
of variation:
2 C
4F
Targeted at
Targeted at
24 C
75F
Targeted
Targeted
between
between
24 and 25C
75 and 77F
Targeted
Targeted
between
between
24 and 26 C
75 and 79F
242 C
754F
252 C
774F
262 C
794F
4.3 Air Conditioning Conditions
Humidity
Remarks
%
455%
About 45% at
The
24C (75F)
temperature
and humidity
About 43% at
depend on
24C (75F)
the thermal
load.
About 40% at
Do not
26C (79F)
change the
flow rate
even if the
underfloor
temperature
is changed.
40 to 50%
Do not
change the
40 to 48%
flow rate
even if the
40 to 45%
underfloor
temperature
is changed.
41