Table 6.3 Transformers For 200 V Server Systems - Fujitsu M10 Series Installation Planning Manual

Hide thumbs Also See for M10 Series:
Table of Contents

Advertisement

CHAPTER 6 Power Supply Facilities
(2) Systems that can tolerate a service disruption
If a server system can tolerate a service disruption caused by power interruption or
voltage variation, install a transformer dedicated to that system, isolated from the
secondary terminals if the system runs at 200 V or grounded to a neutral phase wire if
it runs at 400 V.
a) Transformers dedicated to 200 V server systems
Table 6.3
server systems and their schematic views.
Case
A dedicated high-to-low-voltage
transformer can be installed.
High-to-low-voltage
transformer that is shared with
other power supplies.
70
contains descriptions of the types of transformers dedicated to 200 V

Table 6.3 Transformers for 200 V server systems

Transformer dedicated
to a server system
Install a contact
prevention transformer
that has an output voltage
of 200 V and is dedicated
to the server system. The
secondary terminal of the
transformer shall be
isolated.
Install a separate
transformer that has an
output voltage of 200 V
and is dedicated to the
server system near the
distribution panel. The
secondary terminal of the
transformer shall be
isolated.
Schematic view
High-voltage line
High-voltage line
C120-H007-08EN