5.4.24 BFM#128: Over-scale status data automatic transfer-to data register specification

Use this function to automatically transfer the over-scale status data (BFM#28) to the data register specified
in BFM#128.
When over-scale is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
→ For a detailed description of the over-scale status data (BFM#28), refer to Subsection 5.4.11.
1. If "BFM#128 = K210 (initial value)"
Specified data register
D210
2. Cautions regarding over-scale status data automatic transfer-to data register specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the over-scale status data automatic transfer function (b7 of BFM#22).
• The data written to BFM#128 will be retained in the EEPROM.
3. Caution regarding EEPROM writing
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.

5.4.25 BFM#129: Error status data automatic transfer-to data register specification

Use this function to automatically transfer the error status data (BFM#29) to the data register specified in
BFM#129.
When an error is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
→ For a detailed description of the error status data (BFM#29), refer to Subsection 5.4.12.
1. If "BFM#129 = K211 (initial value)"
Specified data register
D211
2. Cautions regarding error status data automatic transfer-to data register specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the error status data automatic transfer function (b8 of BFM#22).
• The data written to BFM#129 will be retained in the EEPROM.
3. Caution regarding EEPROM writing
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
PLC User's Manual - Analog Control Edition
Description
Over-scale status data in BFM#28
Description
Error status data in BFM#29
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
Setting range: 0 to 7999
Initial value (at delivery) : K210
Numeric data type: Decimal (K)
Setting range: 0 to 7999
Initial value (at delivery) : K211
Numeric data type: Decimal (K)
B-45