Mitsubishi Electric FX3G User Manual page 290

Hide thumbs Also See for FX3G:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
FX
-4DA-ADP (4-channel Analog Output)
3U
2.4.2
When connected to a FX
1. D/A conversion and special data register update timing
D/A conversion is performed at every scan time of the PLC.
During execution of the END instruction, the PLC writes the output setting data of the special data registers,
performs D/A conversion of the data, and updates the analog output data.
FX
-4DA-ADP
3U
2nd
D/A
conversion
250 s/4ch
2. D/A conversion during PLC stop
If the output holding function cancellation setting is enabled by the special device, the offset value will be
output.
If the output holding function cancellation setting is disabled, the output at switching from RUN to STOP will
be latched.
Just after power-on, however, the offset value will be output until operation begins.
3. If two analog special adapters are connected
During execution of the END instruction, data in all the connected adapters will be subject to D/A conversion
and then output (in the order of 1st adapter → 2nd adapter).
4. D/A conversion speed (data update time)
During execution of END instruction, the output setting digital data per of 4 channel will be subject to D/A
conversion which takes 250 μs, after which the analog data will be output.
END instruction execution time will be "250 μs × number of connected adapters".
F-10
PLC User's Manual - Analog Control Edition
3UC
/FX
3G
3GC
FX
-4DA-ADP
3U
conversion
250 s
PLC
1st
Digital value
D/A
writing
D/A conversion
start command
/4ch
Digital value writing
D/A conversion
start command
2.4 D/A Conversion Time
FX
/FX
Series PLC
3G
3GC
Sequence
program
END instruction
2 Specifications

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3sFx3gcFx3uFx3uc

Table of Contents