GE N60 UR Series Instruction Manual page 144

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

5.2 PRODUCT SETUP
j) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
IEC 60870-5-104
PROTOCOL
5
The N60 supports the IEC 60870-5-104 protocol. The N60 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the N60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the N60 at one time.
The
IEC ------- DEFAULT THRESHOLD
M_ME_NC_1 analog data. These settings group the N60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the N60 when any current values change by 15 A, the
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the N60, the default thresholds will be in effect.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the
setting is set to "Enabled", the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
k) SNTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
SNTP PROTOCOL
The N60 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the N60 can obtain clock time
over an Ethernet network. The N60 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported.
5-30
COMMUNICATIONS
IEC 60870-5-104
FUNCTION: Disabled
IEC TCP PORT
MESSAGE
NUMBER: 2404
IEC NETWORK
MESSAGE
CLIENT ADDRESSES
IEC COMMON ADDRESS
MESSAGE
OF ASDU:
IEC CYCLIC DATA
MESSAGE
PERIOD:
IEC CURRENT DEFAULT
MESSAGE
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
MESSAGE
THRESHOLD: 30000
IEC POWER DEFAULT
MESSAGE
THRESHOLD: 30000
IEC ENERGY DEFAULT
MESSAGE
THRESHOLD: 30000
IEC OTHER DEFAULT
MESSAGE
THRESHOLD: 30000
settings are used to determine when to trigger spontaneous responses containing
COMMUNICATIONS
SNTP FUNCTION:
Disabled
SNTP SERVER IP ADDR:
MESSAGE
0.0.0.0
SNTP UDP PORT
MESSAGE
NUMBER: 123
N60 Network Stability and Synchrophasor Measurement System
IEC 60870-5-104 PROTOCOL
Range: Enabled, Disabled
Range: 1 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
0
Range: 1 to 65535 s in steps of 1
60 s
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
IEC CURRENT DEFAULT THRESHOLD
SNTP PROTOCOL
Range: Enabled, Disabled
Range: Standard IP address format
Range: 0 to 65535 in steps of 1
5 SETTINGS
set-
IEC 60870-5-104 FUNCTION
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents