B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 19 of 54)
ADDR
REGISTER NAME
5494
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
B
Open Pole Detect (Read/Write Grouped Setting)
6040
Open Pole Detect Function
6041
Open Pole Detect Block
6042
Open Pole Detect A Aux Co
6043
Open Pole Detect B Aux Co
6044
Open Pole Detect C Aux Co
6045
Open Pole Detect Current Source
6046
Open Pole Detect Current Pickup
6047
Open Pole Detect Voltage Source
6048
Open Pole Detect Voltage Input
6049
Open Pole Detect Pickup Delay
604A
Open Pole Detect Reset Delay
604B
Open Pole Detect Target
604C
Open Pole Detect Events
604D
Open Pole Detect Broken Co
Overfrequency (Read/Write Setting) (4 modules)
64D0
Overfrequency 1 Function
64D1
Overfrequency 1 Block
64D2
Overfrequency 1 Source
64D3
Overfrequency 1 Pickup
64D4
Overfrequency 1 Pickup Delay
64D5
Overfrequency 1 Reset Delay
64D6
Overfrequency 1 Target
64D7
Overfrequency 1 Events
64D8
Reserved (4 items)
64DC
...Repeated for Overfrequency 2
64E8
...Repeated for Overfrequency 3
64F4
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
65CB
Power Swing Detect Delay 1 Pickup
65CC
Power Swing Detect Delay 1 Reset
65CD
Power Swing Detect Delay 2 Pickup
65CE
Power Swing Detect Delay 3 Pickup
65CF
Power Swing Detect Delay 4 Pickup
65D0
Power Swing Detect Seal In Delay
65D1
Power Swing Detect Trip Mode
65D2
Power Swing Detect Block
65D3
Power Swing Detect Target
B-26
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0 to 1
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 5
---
1
0.05 to 20
pu
0.01
0 to 5
---
1
0 to 1
---
1
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 5
---
1
20 to 65
Hz
0.01
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 1
---
1
0.05 to 30
pu
0.001
0.1 to 500
ohms
0.01
40 to 90
degrees
1
0.1 to 500
ohms
0.01
40 to 90
degrees
1
40 to 140
degrees
1
40 to 140
degrees
1
40 to 140
degrees
1
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 65.535
s
0.001
0 to 1
---
1
0 to 65535
---
1
0 to 2
---
1
APPENDIX B
FORMAT
DEFAULT
F203
(none)
F203
(none)
F203
(none)
F203
(none)
F203
(none)
F102
0 (Disabled)
F300
0
F300
0
F300
0
F300
0
F167
0 (SRC 1)
F001
20
F167
0 (SRC 1)
F102
0 (Disabled)
F001
60
F001
100
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F300
0
F167
0 (SRC 1)
F001
6050
F001
500
F001
500
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F513
0 (Two Step)
F001
600
F001
5000
F001
75
F001
5000
F001
75
F001
120
F001
90
F001
60
F001
30
F001
50
F001
17
F001
9
F001
17
F001
400
F514
0 (Delayed)
F300
0
F109
0 (Self-reset)
GE Multilin