7 COMMANDS AND TARGETS
PATH: COMMANDS

RELAY MAINTENANCE

COMMANDS
RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands are activated by changing a command setting
to "Yes" and pressing the ENTER key. The command setting will then automatically revert to "No".
The
command turns on all faceplate LEDs and display pixels for a short duration. The
PERFORM LAMPTEST
command causes the relay to scan the backplane for the hardware modules and update the order code to
ORDER CODE
match. If an update occurs, the following message is shown.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the
message will be shown.
CODE NOT UPDATED
PATH: COMMANDS
PMU ONE-SHOT
COMMANDS
PMU ONE-SHOT
This feature allows pre-scheduling a PMU measurement at a specific point in time. This functionality can be used to test for
accuracy of the PMU, and for manual collection of synchronized measurements through the system, as explained below.
When enabled, the function continuously compares the present time with the pre-set
times match, the function compares the present sequence number of the measured synchrophasors with the pre-set
ONE-SHOT SEQUENCE NUMBER
the corresponding protocol data items for 30 seconds. This allows manual read-out of the synchrophasor values for the pre-
set time and pre-set sequence number (via the faceplate display, supported communication protocols such as Modbus or
DNP, and the EnerVista UR Setup software).
When freezing the actual values the function also asserts a
configured to drive an output contact and trigger an external measuring device such as a digital scope with the intent to ver-
ify the accuracy of the PMU under test.
With reference to the figure below, the PMU one-shot function (when enabled) controls three FlexLogic™ operands:
The
PMU ONE-SHOT EXPIRED
is at least 30 seconds past the scheduled one-shot time.
The
PMU ONE-SHOT PENDING
before the scheduled one-shot time.
The
operand indicates the one-shot operation and remains asserted for 30 seconds afterwards.
PMU ONE-SHOT OP
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
PERFORM LAMPTEST?
No
UPDATE ORDER CODE?
No
UPDATING...
PLEASE WAIT
PMU ONE-SHOT
FUNCTION: Disabled
PMU ONE-SHOT
SEQUENCE NUMBER: 0
PMU ONE-SHOT TIME:
2005/06/14 7:58:35
. When the two numbers match, the function freezes the synchrophasor actual values and
operand indicates that the one-shot operation has been executed, and the present time
operand indicates that the one-shot operation is pending; that is, the present time is
Range: No, Yes
Range: No, Yes

7.1.6 PHASOR MEASUREMENT UNIT ONE-SHOT

Range: Enabled, Disabled
Range: 0 to nominal frequency – 1 in steps of 1
Range: 24h time format
PMU ONE-SHOT TIME
FlexLogic™ operand. This operand may be
PMU ONE-SHOT OP
7.1 COMMANDS
7.1.5 RELAY MAINTENANCE
UPDATE
ORDER
. When the two
PMU
7-3
7