Siemens 7SG11 Manual page 149

Hide thumbs Also See for 7SG11:
Table of Contents

Advertisement

FUN
INF
Description
164
119
Hot line working
164
129
Reset Energy Meters
164
130
Reset Maximum Demand
255
0
Initiate General Interrogation
255
0
Time Synchronisation
Note: Events listing a GI cause of transmission can be raised and cleared; other events are raised only.
3.2
Modbus RTU Definitions
The following tables give information for MODBUS RTU access to IEC 60870-5-103 protocol data. A detailed
description of all protocol information is available in report no 434/TM/5/13 which can be accessed on the
www.reyrolle-protection.com
The tables below detail the MODBUS address map, listing data points that are available and the functions
supported for access. Please note, not all addresses will apply to all models.
To configure MODBUS a new setting has been added to the communications sub-menu to select the protocol to
use, either IEC60870-5-103 or MODBUS-RTU. After selecting MODBUS, set the remaining parameters, baud
rate, parity, station (slave) address, line idle and data echo as appropriate.
When an electrical RS485 module is connected to the Argus relay, the Line Idle and Data Echo settings must
both be set to OFF.
Table showing Coil Addresses
MODBUS
IEC
IEC
Address
FUN
INF
00016
160
16
00019
160
19
00023
160
23
00024
160
24
00025
160
25
00026
160
26
01059
164
35
01060
164
36
01061
164
37
01062
164
38
01075
164
51
01076
164
52
01077
164
53
01078
164
54
©2010 Siemens Protection Devices Limited
in publications section under technical reports, "communications interface manual".
Description
Autoreclose
Reset Flag & Outputs *
Settings Group 1 Select
Settings Group 2 Select
Settings Group 3 Select
Settings Group 4 Select
Settings Group 5 Select
Settings Group 6 Select
Settings Group 7 Select
Settings Group 8 Select
Energise Output 1
Energise Output 2
Energise Output 3
Energise Output 4
7SG11 Argus 1 Diagrams and Parameters
COM
TYP
COT
ON/OFF
20
20
ON/OFF
20
20
ON/OFF
20
20
-
7
9
-
6
8
COM
ON/OFF
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
ON
x
x
-
x
x
P20008 Page 23 of 33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sg11Argus 7sg116