Pressure Controlled Supply Fan + Esm Fixed Speed - Siemens G120P Manual

Variable speed drive
Hide thumbs Also See for G120P:
Table of Contents

Advertisement

Parameter
Value
p2293
30 s
4.3
Macro 105 "Pressure controlled supply fan + ESM
fixed speed"
Pressure in air duct regulated by integrated PID
controller
Flying restart and automatic restart activated
Essential service mode (in the event of fire) with
fixed frequency
Error message: Digital output 0
Status display: Digital output 2
When selecting this application using macro 105, the
technological unit remains unchanged at [%]. If
necessary, adapt the unit as described in the parameter
list. Select the values depending on the used sensor.
Note:
In the case of the extended emergency mode, the
customer can no longer lodge any claims for warranty.
Extended emergency mode and the faults which arise
during this mode are logged in a password-protected
memory and can be read by the repair center.
Parameter
Value
p596
500
p0010
5
p595
5
p0010
0
p756[0]
0
p0840
r722.0
p1015[0]
1350 rpm
p1113[0]
0
p1200[0]
1
p1210
26
p2200[0]
1
p2201[0]
200 Pa
p2253[0]
p2201
p2257
30 s
p2258
30 s
p2264[0]
r755[0]
p2265
10 s
p2267
600 Pa
p2268
-50 Pa
p2293
30 s
p3880
r722.1
p3881
1
Siemens AG
Description
Technology controller ramp-up/ramp-down time

Pressure controlled supply fan + ESM fixed speed

Pressure
sensor 0-
10V, e.g.
QBM66.202
Description
Reference variable of the technological unit
Parameter filter change, technological unit
Selection of technological unit: Pa
Parameter filter ready
Unipolar voltage input (0...10 V)
ON / OFF (OFF1)
Fixed speed setpoint 15
Setpoint inversion
Flying restart always active (start in setpoint direction)
Acknowledging all faults and restarting for an ON command
Technology controller enable
Technology controller fixed value 1
Technology controller setpoint 1
Technology controller setpoint ramp-up time
Technology controller setpoint ramp-down time
Technology controller actual value
Technology controller actual value filter time constant
Technology controller upper limit actual value
Technology controller lower limit actual value
Technology controller ramp-up/ramp-down time
ESM activation
ESM setpoint source: Fixed setpoint 15 (p1015)
Application examples
Pressure controlled supply fan + ESM fixed speed
9
P24V
5
ON / OFF
DI0
6
ESM Activation
DI1
28
GND
69
DI COM
2
GND
4
AI0-
0 - 10 V
3
AI0+
14
PTC A
15
PTC B
4
12
Speed
AO0+
13
(0..20mA)
AO0-
26
Output current
AO1+
27
(0..20mA)
AO1-
20
19
DO0
Fault
18
22
Alarm
DO1
21
25
24
Operation
DO2
23
Optional
39
CM2G5111en
2014-05-16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents