Hardware Diagnostics; Tests Without A Power Supply - Siemens G120P Manual

Variable speed drive
Hide thumbs Also See for G120P:
Table of Contents

Advertisement

Number
Cause
F30052
Incorrect Power Module data
F30662
CU hardware fault
F30664
CU power up aborted
F30850
Software fault in Power Module
F30059
Internal fan defective
6.4
6.4.1
Siemens AG
Solution
Replace the Power Module.
Update the CU firmware.
Switch the CU off and on again.
Update the firmware.
Contact Technical Support.
Switch the CU off and on again.
Update the firmware.
Contact Technical Support.
Replace the Power Module.
Contact Technical Support.
Check the internal fan and replace it, if necessary.

Hardware diagnostics

DANGER
Electrical voltage can result in death or serious injury.
Tests may only be carried out on a drive by personnel who are trained in
working with voltages of up to 600 V AC and 1800 V DC.
Ensure that the drive is grounded correctly.
Switch off the supply line to the drive before carrying out work on the drive or
on any of its parts.
Isolate the power supply to the drive before carrying out work on the drive or
on any of its parts.
After switching off the power supply, wait at least 5 minutes for the capacitor
to discharge completely.
The following devices are required for conducting the tests:
1. Digital multimeter, preferably with a scale for PWM voltage (e.g., Fluke 87)
2. PC with the latest version of STARTER
3. IOP (Intelligent Operator Panel)

Tests without a power supply

CAUTION
Risk of electric current
If the terminals are not accessible externally, do not open the device because you
will be exposed to a great risk and this will invalidate the warranty.
In this case, contact your local Siemens branch office.
Fault rectification
6
Hardware diagnostics
53
CM2G5111en
2014-05-16