CHAPTER 2 Connected Information
(High-efficiency/Standard) 200V Redundant (N+1)
It is necessary to arrange four PSUs, two FANUs, four Power cables (200 V IEC60320 C20) and two power
distribution boxes (200 V IEC60320 C19×3type) for (High-efficiency/Standard) 200V Redundant (N+1).
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution
panel. See
"2.6 Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution
FIGURE 2.25 PRIMEQUEST 2400E3 with Memory Scale-up Board/2800E3/2800B3/2400E2 with Memory
Scale-up Board/2800E2/2800B2/2800E/2800B (High-efficiency/Standard) 200V Redundant (N+1)
Number
(1)
Power distribution box (200V C 19 3 type)
Description
46
box)."
CA92344-0535-06