The terminal designation is given in
Item
1
2
3
4
5
6
7
The terminal explanation is given next:
1
Digital input 1 and 2
The digital inputs can be used for three different functions:
· Implementation of remote control functionality;
· Implementation of local on/off buttons (not provided);
· Selection of main filter settings or auxiliary filter settings (e.g. different filter
settings for the day and for the night)
The PQF-Manager is used to associate the required functionality with the chosen digital
input. The digital inputs can also be disabled.
Digital Outputs
(max 110Vdc / 0.3A
or 440Vac / 1.5A)
(15-24Vdc)
(15-24Vdc)
Alarm Outputs N.O.
(max 250Vac / 1.5A)
LOCK
4
Figure 17: PQF-Manager rear side terminal designation
Table
7.
Table 7: Terminal designation
Customer terminals
Digital input 1 and 2
Digital outputs 1 to 6 with one common point
Alarm outputs (2 outputs with complementary signals)
Lock switch
Modbus adapter interface (optional) connection
CAN bus connection interface (routed to PQF-Manager
connector)
Power supply terminals (routed to PQF-Manager
connector)
Manual Power Quality Filter PQFS ç Hardware description 21
Com
Com
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
N.C.
Made in Belgium
PC-ABS
2
3