Setting whether to use FireAlarm function
ACP BACnet provides Fire Alarm function.
After connecting the fire sensor to ACP BACnet DI1, if the fire sensor detects fire, it stops the
operations of all connected equipments except the Chiller.
Caution
Fire Alarm interface
To use the Fire Alarm function, fire sensor needs to be connected to ACP BACnet DI1.
Please refer to each fire sensor product manual for detail usage of fire sensors.
1.
When you press the [SET] button of the ACP BACnet, menu screen will be displayed.
While [FireAlarm] is selected, if you press [SET] button, you can set whether to use the Fire
Alarm.
Network Info
Contents
>
Function
Click
Register FD
SET
button
[Contents]
>
FireAlarm
Click
SET
button
[Set FireAlarm]
NOT(0) / USE(1) : 0
, and press [SET] button again.
0