LG PQNFB17C1 Installation And User Manual page 199

V-net acs
Table of Contents

Advertisement

Set Lower Temperature (Status)
Point number: 30
Object name: SetLowerTempStatus_XXX (XXX: A/C unit address)
Object type: Analog Input
Meaning: This object is used to monitor set lower temperature which the indoor unit is placed.
Present_Value property:
Temperature(°C)
Remarks: This object is for indoor units only, and reports the set lower temperature data
measured by the indoor units.
Mode Lock (Setting)
Point number: 31
Object name: ModeLockCommand_XXX (XXX: A/C unit address)
Object type: Binary Output
Meaning: This object is used to set the mode lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)
Mode Lock (Status)
Point number: 32
Object name: ModeLockStatus_XXX (XXX: A/C unit address)
Object type: Binary Input
Meaning: This object is used to monitor the mode lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)
Functional Specifications ACP BACnet
187

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acp bacnetPqnfb17c0

Table of Contents