LG PQNFB17C1 Installation And User Manual page 86

V-net acs
Table of Contents

Advertisement

Using the Program
74
Registering Device Manually
Devices connected to ACP BACnet can be registered by the user by entering relevant information.
You can register a device manually as follows.
1.
In the main menu, click the [Installing] menu icon.
2.
Click the [Installing] tab.
3.
Type the device information and click the [Insert] button.
Item
Device Type
Unit Name
(20 Characters)
Address (00-
FF)
Model
(20 Characters)
Capacity
(5-digit)
4.
To save the device, click the [Apply Change] button.
Device registration is completed.
Selects a device type.
IDU(indoor unit,), ODU(Outdoor unit,), ERV(Energy Recovery Ventilator),
ERV DX(Direct Expansion Energy Recovery Ventilator ), DI/DO, DOKIT,
AWHP, or AHU
Enter the device name.
Up to 20 characters.
Type the physical address of the device.
A physical address value is a number between 00 and FF. You
cannot type the same value for the same device.
You cannot enter a duplicate value for indoor devices and DOKIT.
Type the device model.
Up to 20 characters.
Type the maximum power consumption of the device.
Up to 5 characters.
The power consumption value of the actual device cannot exceed
the input value.
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acp bacnetPqnfb17c0

Table of Contents