LG PQNFB17C1 Installation And User Manual page 191

V-net acs
Table of Contents

Advertisement

Operation Mode (Setting)
Point number: 7
Object name: ModeCommand_XXX (XXX: Indoor/Vent/AHU address)
Object type: Multistate Output
Meaning: This object is used to set the operation modes of the air conditioner.
Present_Value property:
Indoor
1 : Cool
HEX
2 : Dry
Auto
3 : Fan
Normal
4 : Auto
-
5 : Heat
-
Remarks:
1. The Present_Value property will be set to "1: Cool" as the default value if property has never
been set in the past.
2. The air conditioner will ignore the command to an object that does not have right to select
operation mode. Therefore, the controlled/monitored system must not use this object for the
air conditioner without the right to select operation mode.
Operation Mode (Status)
Point number: 8
Object name: ModeStatus_XXX (XXX: Indoor/Vent/AHU address)
Object type: Multistate Input
Meaning: This object is used to monitor the operation modes of the air conditioner.
Present_Value property:
Indoor
1 : Cool
HEX
2 : Dry
Auto
3 : Fan
Normal
4 : Auto
-
5 : Heat
-
Vent
Vent
Functional Specifications ACP BACnet