Operation
ALARM Procedure
Action / Condition
Step
1
<Press <Acknowledge> on the Person
Machine Interface
2
Read top line on display
– 'Fire Brigade requested'
– 'Fire Brigade in' 'mm:ss'
– 'Call Fire Brigade !'
when:
Remote transmission switched off
Remote transmission blocked or defective
No remote transmission available
3
Read off fire location on display
4
Go to the fire location
5
Decide: MAJOR INCIDENT or minor incident
Condition
Fire department has been
called
'Fire Brigade in' 'mm:ss'
Countdown is running
'Call Fire Brigade !'
No automatic transmission to
the fire department
20
Building Technologies
Fire Safety
Procedure in the event of alarm
MAJOR INCIDENT
Save people
Guide the fire department to the fire
location
Fight the fire
Trigger 'Manual call point' immediately
or
<Press <Alarm delay off>
Call the fire department on the phone!
To reset, the key switch must be used.
It may be necessary to air the room before resetting is possible.
Elements that cannot be reset can be switched off temporarily on the control
panel.
Consequence / Status
With 'AVC', countdown t2 for the examination of the
'ALARM' source starts
'ALARM' is transmitted to the fire brigade
'ALARM' is transmitted to fire brigade in 'mm:ss'
Remaining time is shown as Countdown
Fire brigade must be called by phone!
No automatic transmission to fire brigade
Minor incident
Try to prevent fire department
deployment
<Press <Reset>
<Press <Reset>
<Press <Reset>
009310_i_en_--
2013-11-14