6.5 Switching an object on / off

Building Technologies
Fire Safety
To avoid false alarms, you can switch off parts of a 'Site' in certain situations, e.g.
for the purpose of maintenance work.
When a part of the 'Site' is switched off, the LED 'ISOLATION' is on.
In which situations the pre-configured object should be switched off, depends on
the detectors used as well as on possible deceptive phenomena such as smoke,
dust, heat or vapour.
You can use the <'Section' 'OFF'> button to isolate a preconfigured object at the
touch of a button.
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
Deploy staff to monitor the deactivated area.
You must switch deactivated parts of the 'Site' back on as soon as possible.
If a deactivated 'Zone' is the only 'Zone' in a 'Section', the 'Section' is also
indicated as deactivated.
'Section'
Before you may switch off the pre-configured object, you must release
operation by means of the 'Key switch'.
1. Turn the 'Key switch' into a horizontal position.
Operation is released.
2. Press <'Section' 'OFF'>.
The pre-configured object is isolated.
LED 'ISOLATION' on.
Switching on the object
The object is isolated and the LED 'ISOLATION' is on.
1. Turn the 'Key switch' into a horizontal position.
Operation is released.
2. Press <'Section' 'OFF'>
The pre-configured object is switched on.
LED 'ISOLATION' off.